How to solve the problem of hysteresis in the pressure switch of the lubricating oil pump outlet

    Lubrication oil pump outlet pressure is low from the start switch PSXL-08404 0.6MPa setting value, the switching operation of two pressure very close, so that the lubricating oil pump outlet pressure when the switching operation has little hysteresis, it is possible to cause carbon dioxide compressor jumping first, and then start Oil auxiliary pump.
  
Shorting through the instrument switch, disconnect the experiment, auxiliary pump since the start of a good condition. Through the entire system even school, found that the pump outlet pressure is low when the pressure switch slow. Check the switch did not find abnormal switching. Lubrication pump outlet pressure low Interlock switch take pressure point In the pump outlet, the pressure switch installed in the switchgear, away from the pressure point between the pressure guide tube length of about 8m, and guide tube diameter smaller. When the oil pump outlet pressure is low, due to large pressure guide tube resistance, the measuring element can not be timely pressure relief, resulting in slow switching, the reaction lag, resulting in low oil pressure control interlock switch PSXL-08301, so that the carbon dioxide compressor jumped .
  
From the switching settings, under normal circumstances, the outlet pressure of lubricating oil is 1.2MPa, the control pressure is low, the jumping value of PSXL-08301 is 0.4MPa, the outlet pressure of lubricating oil pump is low, the setting value of PSXL-08404 is 0.6MPa, the two switches Action pressure is very close, so when the lubricant pump outlet pressure switch a little lag, it is possible to cause the first carbon dioxide compressor jumped, and then start the lubricating oil pump.
  
Interlock to improve the program and the effect The key to solve this problem is to reduce the low delay of the oil switch lag, start the auxiliary pump in time. To this end we will change the switch setting value from 0.6MPa to 0.8MPa, so not only reduce the lag time since the start switch, but also widened the interlocking jump value and auxiliary pump self-starting value of the distance, basically to avoid Jumping car switch ahead of the phenomenon. After several years of operation proved to be very successful transformation, not only did not appear to start the auxiliary pump lag phenomenon, there has been no sub-pump start frequently.

For ZAXIS Cylinder Seal Kit

Selection and precautions of hydraulic cylinders for excavators
The hydraulic cylinder of an excavator is one of the important components, which converts hydraulic energy into mechanical energy,
Drive mechanical movement. When purchasing hydraulic cylinders for excavators, the following points should be noted:
1. Size and quality: The size and quality of the excavator hydraulic cylinder should match the model and specifications of the excavator to ensure its normal operation.
2. Pressure and flow rate: The pressure and flow rate of the excavator hydraulic cylinder should match the requirements of the hydraulic system,
To fully utilize the capabilities of the hydraulic system.
3. Sealing performance: The hydraulic cylinder of the excavator has good sealing performance to avoid hydraulic oil leakage or entering the mechanical interior.
4. Durability: The hydraulic cylinder of the excavator has good durability and can withstand long-term heavy load work.
5. Brand and Quality: Choose well-known excavator hydraulic cylinders to ensure their quality and after-sales service


For Zaxis Cylinder Seal Kit,Bucket Cyl Kit,Travel Motor Seal Kit,Middle Arm Cylinder Seal Kit

Safe Seal Technology Co., Ltd. , https://www.aprseal.com